Operating Instructions
Reelcraft Industries, Inc. 2842 E Business Hwy 30, Columbia City, IN 46725
Ph: 800-444-3134 / 260-248-8188 Fax: 800-444-4587 / 260-248-2605
Customer Service: 855-634-9109 [email protected] www.reelcraft.com
Rev: 5/2012
Dimensions
GA3100 N
Static Discharge Reel
Model Number:
A
9.25”
B
4.31”
C
9.75”
A
B
C
Grounding plugs / clamps shall not be allowed to drag across ramp.
Clamps / plugs shall be carried to reels on equipment.
Replace cable with 100’ maximum 3/32” x 5/32” grounding cable, with maximum coating OD of 1/8”.
Pre-wind the reel 54 to 55 full turns clockwise. Attach cable and allow it to slowly retract into the
reel.
Do not operate this product without the appropriate pre-wind on the reel. Over pre-winding or under
pre-winding of the reel may damage the power spring.
Failure to follow the above warnings may cause personal injury and damage to the reel.